# Omron FINS TCP

Omron Fins TCP is a protocol for communication between Omron PLCs and other devices. It is a TCP/IP based protocol. The fins driver is used for Omron PLCs with network port, such as CP2E.

For the generic steps, see [Create a Southbound Driver](../south-devices.md) and [Groups and Tags](../../groups-tags/groups-tags.md).

EMQX Neuron supports Fins TCP protocol, which can be used to communicate with Omron PLCs through Fins TCP protocol.

## Add Driver

On **Data Collection → South Devices**, click **Add Device**.

- Name: The name of this device node.
- Driver: Select the **Omron FINS TCP** driver.

## Connection Parameters

Click the driver card to open the **Device Configuration** page and fill in:

| Parameter          | Description                                   |
| ------------------ | --------------------------------------------- |
| **Equipment Type** | Target PLC Equipment type                     |
| **PLC IP Address** | Target PLC IPv4 address                       |
| **PLC Port**       | Target PLC port, default 9600                 |
| **Max Size**       | Maximum byte length of the packet, default 64 |

## Tag Configuration

The data types and address formats supported by this driver are listed below.

### Data Types

* UINT8
* INT8
* INT16
* UINT16
* INT32
* UINT32
* FLOAT
* INT64
* UINT64
* DOUBLE
* BIT
* STRING

### Address Format

> AREA ADDRESS\[.BIT]\[.LEN\[H]\[L]]

#### AREA ADDRESS

| AREA | DATA TYPE                                               | ATTRIBUTE  | REMARK           |
| ---- | ------------------------------------------------------- | ---------- | ---------------- |
| CIO  | All types except uint8/int8                             | read/write | CIO Area         |
| A    | All types except uint8/int8                             | read       | Auxiliary Area   |
| W    | All types except uint8/int8                             | read/write | Work Area        |
| H    | All types except uint8/int8                             | read/write | Holding Area     |
| D    | All types except uint8/int8                             | read/write | Data Memory Area |
| P    | All types except uint8/int8, but bit only supports read | read/write | PVs              |
| F    | int8/uint8                                              | read       | Flag Area        |
| EM   | All types except uint8/int8                             | read/write | Extended Memory  |

*Example:*

| Address  | Data Type | Description               |
| -------- | --------- | ------------------------- |
| F0       | uint8     | F area, address is 0      |
| F1       | int8      | F area, address is 1      |
| CIO1     | int16     | CIO area, address is 1    |
| CIO2     | uint16    | CIO area, address is 2    |
| A2       | int32     | A area, address is 2      |
| A4       | uint32    | A area, address is 4      |
| W5       | float     | W area, address is 5      |
| W10      | float     | W area, address is 10     |
| H20      | double    | H area, address is 20     |
| H30      | uint32    | H area, address is 30     |
| D10      | int32     | D area, address is 10     |
| D20      | float     | D area, address is 20     |
| EM10W100 | float     | EM10 area, address is 100 |

#### .BIT

Optional, referring to a bit of an address.

#### .LEN\[H]\[L]

When the data type is string type, it is a required, **`.LEN`** indicates the length of the string, including **H** and **L** two endianness, the default is **H**.

### Example Addresses

| Address     | Data Type | Description                                                                    |
| ----------- | --------- | ------------------------------------------------------------------------------ |
| CIO0.0      | bit       | CIO area, address is 0, bit 0                                                  |
| CIO1.2      | bit       | CIO area, address is 1, bit 2                                                  |
| A2.1        | bit       | A area, address is 2, bit 1                                                    |
| A2.3        | bit       | A area, address is 2, bit 3                                                    |
| W3.4        | bit       | W area, address is 3, bit 4                                                    |
| W3.0        | bit       | W area, address is 3, bit 0                                                    |
| H4.15       | bit       | H area, address is 4, bit 15                                                   |
| H4.10       | bit       | H area, address is 4, bit 10                                                   |
| D5.2        | bit       | D area, address is 5, bit 2                                                    |
| D5.3        | bit       | D area, address is 5, bit 3                                                    |
| EM10W100.0  | bit       | EM10 area, address is 100, bit 0                                               |
| CIO0.20     | string    | CIO area, address 0, the string length is 20 bytes and the endianness is L     |
| CIO1.20H    | string    | CIO area, address 1, the string length is 20 bytes and the endianness is H     |
| A2.10L      | string    | A area, address 2, the string length is 10 bytes and the endianness is L       |
| A2.30       | string    | A area, address 2, the string length is 30 bytes and the endianness is L       |
| W3.40H      | string    | W area, address 3, the string length is 40 bytes and the endianness is H       |
| W3.10       | string    | W area, address 3, the string length is 10 bytes and the endianness is L       |
| H4.15L      | string    | H area, address 4, the string length is 15 bytes and the endianness is L       |
| H4.10       | string    | H area, address 4, the string length is 10 bytes and the endianness is L       |
| D5.20H      | string    | D area, address 5, the string length is 20 bytes and the endianness is H       |
| D5.30       | string    | D area, address 5, the string length is 30 bytes and the endianness is L       |
| EM10W200.10 | string    | EM 10 area, address 200, the string length is 10 bytes and the endianness is L |

## Use Case