CODESYS V3 TCP
The Neuron CODESYS V3 TCP plugin enables access to PLCs and motion control systems based on the CODESYS V3 platform through the TCP protocol.
Device Settings
| Field | Description |
|---|---|
| host | Device IP address |
| port | Device port, default is 11740 |
| timeout | Request send/receive timeout, default is 3000ms |
| username | Device username |
| password | Device password |
Supported Data Types
- uint8
- int8
- uint16
- int16
- uint32
- int32
- float
- bool
- string Type Mapping Table
| CODESYS V3 | Neuron |
|---|---|
| Bool | bool |
| Byte | uint8 |
| SInt | int8 |
| USInt | uint8 |
| Word | uint16 |
| Int | int16 |
| UInt | uint16 |
| DWord | uint32 |
| DInt | int32 |
| Real | float |
| UDInt | uint32 |
| String | string |
ADDRESS
TAG NAME
The symbol configuration exported by the CODESYS V3 platform is the address of the Nueron location.
Address Examples
| Address | Data Type | Description |
|---|---|---|
| Application.PLC_PRG.ok | bool | Boolean flag |
| Application.PLC_PRG.d1arr[1] | int16 | Value of index 1 in a 1D array |
| Application.PLC_PRG.d2arr[1,1] | int32 | Value of index 1,1 in a 2D array |
| Application.PLC_PRG.d3arr[1,1,1] | int16 | Value of index 1,1,1 in a 3D array |
| Application.PLC_PRG.point.Y | float | Y variable value of the Point structure |
| Application.PLC_PRG.points[1].Name | string | Name variable value of the Point structure array at index 1 |