Connect to FP-XH C30T
Configurator WD
Go to https://www3.panasonic.biz/ac/e/fasys/software_info/common/tol_configwd.jsp and download configurator_wd_v177.exe after registration and install it.
Open the Configurator WD software, click on the menu
Option->Select IP of PC->Specify the IP address of PC, select the local IP address and click on theOKbutton.
Click on the menu
Search->Search BroadCast, the FP-X COM5 module will appear in the list.
Right click on the FP-X COM5 item in the list and select
Setting IP Addressin the pop-up menu to set a fixed IP address for the PLC device, then clickOK.
Right click on the FP-X COM5 item in the list, select
Communication Settingin the pop-up menu, set theBaud rate of COM1to115200and clickOK.
Right-click on the FP-X COM5 item in the list, select
Communication Setting->Option Settingin the pop-up menu, setRespons timeoutto1000and clickOK.
Open Control FPWIN Pro 7 and confirm that the
Communication Speedof the PLC serial portCOM1is115200.
Neuron Setting
Add a Panasonic Mewtocol device to the Neuron Southbound Device Manager. 2.
Change
PLC IP Addressto the target device IP address in the device configuration. 3.Modify
PLC Portto be the target device port in the device configuration. 4.Change
Unit Numberto the target device unit number in the device configuration and submit the setup form.
Test Data List
| Name | Address | Attribute | Data type |
|---|---|---|---|
| DATA1 | DT0 | Read Write | INT16 |
| DATA2 | DT2 | Read Write | UINT16 |
| DATA3 | DT4 | Read Write | INT32 |
| DATA4 | DT7 | Read Write | UINT32 |
| DATA5 | DT10 | Read Write | FLOAT |
| DATA6 | DT13 | Read Write | DOUBLE |
| DATA7 | X0 | Read | BIT |
| DATA8 | Y0 | Read Write | BIT |
| DATA9 | DT20.0 | Read | BIT |
| DATA10 | DT17.20 | Read Write | STRING |