Modbus RTU FAQ 
Unable to Read Tag Value, Error Code 3002 
- Enable DEBUG logging, check the log, inspect the data flow, and verify if the device has responded with data. If there is a response, check if the data is correct (serial devices may produce exceptions when multiple upstream masters collect data).
 - Check if the station number is correct.
 - Verify if the address is correct (Modbus address for Neuron starts from 1).
 - Some devices may not support reading a single point at a time, so all points need to be configured (Neuron automatically optimizes batch reading).
 - Serial wiring issues.
 - Incorrect serial port configuration.
 - The device supports Modbus TCP protocol instead of Modbus RTU. Try using Modbus TCP plugin.
 
Tag Value Invalid, Error Code 3008 
- The device is offline, and data cannot be updated.
 - The device does not respond with data within a certain period.
 - The device supports Modbus TCP protocol instead of Modbus RTU. Try using Modbus TCP plugin.
 
Tag Value Read does not Match Expecations 
- Incorrect data type.
 - Incorrect byte order.
 - Presence of multiple upstream masters collecting data resulting in data corruption.
 - The DTU has enabled registration or heartbeat packets, causing Neuron to consider data flow data as incorrect.
 - The device actively uploads data, but the standard Modbus only supports requesting and then responding with corresponding data.
 - The device supports Modbus TCP protocol instead of Modbus RTU. Try using Modbus TCP plugin.