Read & Write
Read Tag
POST /api/v2/read
Request Headers
Content--Type application/json
Authorization Bearer <token>
Response Status
- 200
Body
{
//node name (required)
"node": "modbus-tcp-1",
//group name (required)
"group": "config_modbus_tcp_sample_2",
//synchronous read (optional, default false)
"sync": false,
//filter (optional)
"query": {
//tag name substring match (optional)
"name": "data",
//tag description substring match (optional)
"description": "switch"
}
}
Response
{
"tags": [
{
//tag nmae
"name": "data1",
//tag value
"value": 1,
},
{
"name": "data2",
"error": 2014
},
{
"name": "data3",
"value": true,
}
]
}
TIP
The value is displayed only when the value is read correctly, when the value is read incorrectly, the error code is displayed, not the value.
Read Tag(pagination)
POST /api/v2/read/paginate
Request Headers
Content--Type application/json
Authorization Bearer <token>
Response Status
- 200
Body
{
//node name (required)
"node": "modbus-tcp-1",
//group name (required)
"group": "config_modbus_tcp_sample_2",
//synchronous read (optional, default false)
"sync": false,
//filter (optional)
"query": {
//tag name substring match (optional)
"name": "data",
//tag description substring match (optional)
"description": "switch",
//current page (optional)
"currentPage": 1,
//number of tags per page (optional)
"pageSize": 10,
//response error tags only (optional)
"isError": true
}
}
Response
{
"meta": {"currentPage": 1, "pageSize": 10, "total": 1},
"items": [ {
"name": "tag1",
"type": 4,
"address": "1!400001",
"attribute": 8,
"description": "",
"precison": 0,
"decimal": 0,
"bias": 0,
"error": 3002 // "value": 123
} ]
}
TIP
The value is displayed only when the value is read correctly, when the value is read incorrectly, the error code is displayed with error.
TEST Reading Tag
POST /api/v2/read/test
Request Headers
Content--Type application/json
Authorization Bearer <token>
Response Status
- 200
Body
{
"driver": "1",
"group": "1",
"tag": "tag1",
"address": "1!400002",
"attribute": 8,
"type": 3,
"precision": 0,
"decimal": 0,
"bias": 0.0
}
Response
{
"value": 29540
}
{
"error": 3022
}
TIP
Only perform reading tests, no need to actually add the tag. Not compatible with tag and node byte order, does not calculate decimal and offset.
Write Tag
Write One Tag
POST /api/v2/write
Request Headers
Content-Type application/json
Authorization Bearer <token>
Response Status
- 200 OK
Body
{
"node": "modbus-tcp-1",
"group": "config_modbus_tcp_sample_2",
"tag": "tag1",
"value": 1234
}
Response
{
"error": 0
}
Write Multiple Tags
POST /api/v2/write/tags
TIP
Multiple tags writing currently only supports Mitsubishi 3E, Beckhoff ADS, Modbus TCP, Modbus RTU, Siemens S7 ISOTCP, Omron FINS TCP, OPC UA, BACnet/IP drivers.
Request Headers
Content-Type application/json
Authorization Bearer <token>
Response Status
- 200 OK
Body
{
"node": "modbus-tcp-1",
"group": "group1",
"tags": [
{
"tag": "tag1",
"value": 123
},
{
"tag": "tag2",
"value": 1233
},
{
"tag": "tag3",
"value": 7788
},
{
"tag": "tag4",
"value": 1
},
{
"tag": "tag5",
"value": "asdfda"
}
]
}
Response
{
"error": 0
}