GE SRTP
Neuron GE SRTP plugin accesses GE PLC devices that support SRTP over TCP.
Parameter Configuration
Parameter | Description |
---|---|
host | PLC IP address |
port | PLC port, default 18245 |
timeout | Timeout for sending requests to the device, default 3000 ms |
Support Data Type
- uint8
- int8
- uint16
- int16
- uint32
- int32
- uint64
- int64
- float
- double
- bit
- string
ADDRESS
AREA ADDRESS[.BIT][.LEN]
.BIT
Optional, referring to a bit of an address, range 0 - 15.
.LEN
When the data type is a string type, it is required and indicates the length of the string.
ADDRESS AREA
AREA | DATA TYPE | ATTRIBUTE | PLC AREA |
---|---|---|---|
%I | int8/uint8/bit | R | Discrete inputs |
%Q | int8/uint8/bit | R/W | Discrete outputs |
%M | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | Internal references |
%T | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | Temporary references |
%SA | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | System status references A |
%SB | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | System status references B |
%SC | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | System status references C |
%S | int8/uint8/int32/uint32/int64/uint64/float/double/bit | R/W | System status references |
%G | int32/uint32/int64/uint64/float/double/bit | R/W | Discrete globals |
%AI | int32/uint32/int64/uint64/float/double/bit | R | Analog input registers |
%AQ | int32/uint32/int64/uint64/float/double/bit | R/W | Analog output registers |
%R | int32/uint32/int64/uint64/float/double/bit/string | R/W | System register reference |
Address Examples
ADDRESS | DATA TYPE | Des |
---|---|---|
%I100 | bit | %I100 |
%I100 | uint8 | %I100~%I107 |
%Q200 | bit | %Q200 |
%Q200 | uint8 | %Q200~%Q207 |
%R100 | int16 | %R100 |
%AI100 | float | %AI100 float |
%R10 | double | %R10 double |
%R100.2 | bit | %R area, the starting data word is 100, bit 2 |
%R200.12 | string | %R area, the starting data word is 200, a string of 12 characters |