HollySys Modbus RTU ​

The EMQX Neuron HollySys Modbus RTU driver is for collecting HollySys PLC tags using the Modbus RTU protocol,

For the generic steps, see Create a Southbound Driver and Groups and Tags.

Add Driver ​

On Data Collection → South Devices, click Add Device.

  • Name: The name of this device node.
  • Driver: Select the HollySys Modbus RTU driver.

Connection Parameters ​

Click the driver card to open the Device Configuration page and fill in:

ParameterDescription
Physical LinkSelects the communication medium, either serial or Ethernet.
Connection TimeoutThe time the system waits for a device to respond to a command.
Maximum Retry TimesThe maximum number of retries after a failed attempt to send a read command.
Retry IntervalResend reading instruction interval(ms) after a failed attempt to send a read command.
Send IntervalThe waiting time between sending each read/write command. Some serial devices may discard certain commands if they receive consecutive commands in a short period of time.
Serial DeviceOnly needed in Serial mode, the path to the serial device when using a serial connection, e.g., /dev/ttyS0 in Linux systems.
Stop BitsOnly for the Serial mode, the serial connection parameter.
ParityOnly for the Serial mode, the serial connection parameter.
Baud RateOnly for the Serial mode, the serial connection parameter.
Data BitsOnly for the Serial mode, the serial connection parameter.
Connection ModeOnly for the Ethernet mode, you can choose EMQX Neuron as the TCP client or server.
IP AddressOnly for the Ethernet mode, the IP address of the device when using TCP connection with EMQX Neuron as the client, or the IP address of EMQX Neuron when using TCP connection with EMQX Neuron as the server. The default value is 0.0.0.0.
PortOnly for the Ethernet mode, the port number of the device when using TCP connection with EMQX Neuron as the client, or the port number of EMQX Neuron when using TCP connection with EMQX Neuron as the server.
Maximum Retry TimesThe maximum number of retries after a failed attempt to send a read command.
Retry IntervalResend reading instruction interval(ms) after a failed attempt to send a read command.

The HollySys Modbus RTU driver configuration is similar to that of the Modbus RTU driver module.

Tag Configuration ​

The data types and address formats supported by this driver are listed below.

Data types ​

  • BIT
  • BOOL
  • INT16
  • UINT16
  • WORD

Address format ​

SLAVE!ADDRESS[#ENDIAN]

The address format is nearly the same to that of the Modbus RTU driver module, the only difference is in the ADDRESS part.

SLAVE ​

Required, Slave is the slave address or site number.

ADDRESS ​

HollySys PLC maps data units onto the Modbus address space for access through the Modbus RTU protocol. The EMQX Neuron HollySys Modbus RTU driver frees users from details of the address mapping, and designates the PLC data unit name as the ADDRESS.

AreaData unit exampleAttributeRegister SizeData Type
IX (Input)IX0.0 ... IX0.7, IX1.0 ... IX1.7 ...Read1BitBOOL/BIT
IW (Input Registers)IW0, IW1, ...Read16Bit,2ByteINT16/UINT16
QX (Coils)QX0.0 ... QX0.7, QX1.0 ... QX1.7 ...Read/Write1BitBOOL/BIT
QW (Hold Registers)QW0, QW1, ...Read/Write16Bit,2ByteINT16/UINT16
MX (Coils)MX0.0 ... MX0.7, MX1.0 ... MX1.7 ...Read/Write1BitBOOL/BIT
MW (Hold Registers)MW0, MW1, ...Read/Write16Bit,2ByteINT16/UINT16

#ENDIAN ​

Optional, byte order, applicable to data types int16/uint16, see the table below for details.

SymbolByte OrderSupported Data TypesNote
#B2,1int16/uint16
#L1,2int16/uint16Default byte order if not specified

TIP

The byte order can be illustrated using the notation ABCD, which corresponds directly to the sequence 1234. As an example, the ABCD designation represents the standard or default Endianness 1234. (#LL).

Example Addresses ​

AddressData TypeDescription
1!IX1.0bitData unit IX1.0 on slave 1, read only.
1!QW0int16Data unit QW0 on slave 1, support read/write.
2!MW1int16Data unit MW1 on slave 1, support read/write.