Connect to Industrial Gateway OPC Server ​

Anonymous Login ​

  1. Double click on the Industrial Gateway OPC Server icon in the system tray, open the Project -> Property Editor -> OPC UA, and set Allow anonymous login to Yes. igs-1_en

  2. Right-click the Industrial Gateway OPC Server icon in the system tray, select OPC UA Configuration -> Server Endpoint, double-click the endpoint entry, and check all security policies. igs-2_en

  3. Right-click on the Industrial Gateway OPC Server icon in the system tray and select Reinitialize in the menu.

  4. EMQX Neuron adds a new southbound OPC UA device, opens Device Configuration, fills in the Endpoint URL of the target Server, without filling in username/password, without adding certificate/key, and starts the device connection.

Certificate/Key + Anonymous Login ​

  1. Set up an anonymous login as described above.

  2. Refer to the Connection policy to generate or convert a certificate/key.

  3. Right-click the Industrial Gateway OPC Server icon in the system tray, select OPC UA Configuration -> Trusted Clients, and import the client certificate in DER format into the list.

  1. Right-click on the Industrial Gateway OPC Server icon in the system tray and select Reinitialize in the menu.

Configure EMQX Neuron ​

  1. Get the PLC measurement point information via the UaExpert software, refer to UaExpert. igs-4_en

  2. EMQX Neuron adds a new southbound OPC UA device, opens Device Configuration, fills in the Endpoint URL of the target Server, does not need to fill in the username/password, adds the certificate/key.

  3. Change the Update Mode to Subscribe or Read&Subscribe to obtain data via OPC UA subscription.

  4. Starts the device connection.

  5. Add Groups and Tags based on the measurement point information.

Test Data List ​

NameAddressAttributeData type
BuildDate0!2266ReadUINT32
BuildNumber0!2265ReadSTRING
ManufacturerName0!2263ReadSTRING
ProductName0!2261ReadSTRING
ProductUri0!2262ReadSTRING
SoftwareVersion0!2264ReadSTRING