When the line is already built and SCADA, HMI, MES, historians, and configuration software are all running, this class of northbound application supplies them with the data the gateway collects, without changing those systems.

The direction is the reverse of the other northbound applications: EMQX Neuron does not push data out, it exposes an OPC UA service. Upper-level systems connect in as clients to browse the address space, subscribe to tag changes, read live values, and send control commands back down.

OPC UA is the common interface in industrial automation, and SCADA, HMI, and configuration software generally support it natively. Once connected, the device protocols collected below — Modbus, Siemens S7, Mitsubishi, Omron, CNC controllers, the IEC power series — are presented as a single OPC UA data source. Upper-level systems no longer integrate them one by one, and no OPC driver has to be purchased or comms program written per PLC type. When a southbound driver is added and subscribed in EMQX Neuron, its tags appear in the address space automatically.

Address space structure

EMQX Neuron maps subscribed tags to OPC UA nodes, mirroring the plant structure:

EMQX Neuron
└── modbus-tcp-1          southbound driver → Object node
    └── group-1           collection group  → child Object
        └── temperature   tag               → Variable node

NodeId follows ns=1;s=[device].[group].[tag] — for example ns=1;s=modbus-tcp-1.group-1.temperature. Upper-level systems can generate their tag configuration from that rule instead of browsing by hand.

WARNING

Only tags in subscribed groups appear in the address space. A subscription must be added after creating the application — see Subscribe to Southbound Data — or clients connect but see no variable nodes.

Security configuration

On a plant network OPC UA usually carries control commands, so security configuration is not optional.

ItemDescription
Security policyNone, Basic256Sha256, Basic256, Basic256Rsa15, and Aes128_Sha256_RsaOaep are supported. In production, use Basic256Sha256 and enable SignAndEncrypt on the client
Mutual certificate validationA self-signed server certificate is generated on first start and must be trusted by the client; an unknown client's certificate enters the untrusted list and has to be approved in the UI before it can connect
Username and password authenticationUsers can be added, have passwords updated, and be deleted

Writing back to devices

An OPC UA client writes to a variable node and the value goes down to the device, with no extra topic or channel to configure. The target tag must have the write attribute configured in the southbound driver — see Groups and Tags · Tag attributes.

Selecting an application

ApplicationWhen it applies
OPC UA ServerThe standard route when the upper-level system has an OPC UA client
WebSocketPush to an in-house WebSocket server, for custom dashboards and back ends. This one pushes rather than serving

Connection example

Using UaExpert to Connect to EMQX Neuron OPC UA Server walks through connecting, trusting the certificate, subscribing to variables, and writing values.