Skip to content

OPC AE ​

EMQX Neuron can use the Neuron HUB driver and NeuronHUB Windows program to indirectly access OPC AE (Alarms and Events) servers running on Windows systems, supporting Simple, Conditional, and Tracking events. OPC AE is primarily used to retrieve alarm and event information from devices.

NEURON HUB Windows Program Parameters ​

ParameterDescription
Node NameNode name, must be unique to distinguish multiple nodes
HostTarget host identifier (IP or hostname)
UserNameuser name
PassWrodpassword
Domaindomain
ServerAE server name (e.g., opcae://192.168.10.133/Matrikon.OPC.Alarms). After filling in Host, click the dropdown to fetch server lists.

Supported Data Types ​

  • string

Data example:

json
{
  "source": "GEAK Source",
  "condition": "",
  "subCondition": "",
  "message": "GEAK",
  "time": "2026-01-06T13:40:25.6375708+08:00",
  "severity": 2,
  "eventType": 1,
  "categoryId": 3,
  "ackRequired": false,
  "activeTime": "0001-01-01T00:00:00",
  "newState": 0,
  "actorId": "",
  "clientHandle": "ae",
  "changeMask": 0,
  "quality": 0,
  "cookie": 0,
  "attributes": [
    100,
    200,
    300
  ]
}

Address Format ​

When selecting the OPCAE node type in the Neuron HUB driver, the address is the event source path in the OPC AE server. You can use the Export function to export all point information as a table and import it directly into NEURON.

Alarm Acknowledgment ​

Supports acknowledgment of Conditional alarms and writing comments.