Panasonic Mewtocol

Mewtocol is a Panasonic-developed protocol enabling data exchange between its PLC devices and various others, such as computers and HMI devices

The Mewtocol plugin is used to access Panasonic's FP-XH, FP0H series PLCs via Ethernet.

Add Device

Go to Configuration -> South Devices, then click Add Device to add the driver. Configure the following settings in the popup dialog box.

  • Name: The name of this device node.
  • Plugin: Select the Panasonic Mewtocol plugin.

Device Configuration

After clicking Create, you will be redirected to the Device Configuration page, where we will set up the parameters required for Neuron to establish a connection with the northbound application. You can also click the device configuration icon on the southbound device card to enter the Device Configuration interface.

ParameterDescription
PLC IP AddressTarget PLC IPv4 address
PLC PortTarget PLC IPv4 address, Default 2000
PLC StationTarget PLC station, Default 1
Timeout (ms)Target PLC read timeout

Configure Data Groups and Tags

After the plug-in is added and configured, the next step is to establish communication between your device and Neuron by adding groups and tags to the Southbound driver.

Once device configuration is completed, navigate to the South Devices page. Click on the device card or device row to access the Group List page. Here, you can create a new group by clicking on Create, then specifying the group name and data collection interval.

Upon successfully creating a group, click on its name to proceed to the Tag List page. This page allows you to add device tags for data collection. You'll need to provide information such as the tag address, attributes, and data type.

For information on general configuration items, see Connect to Southbound Devices. The subsequent section will concentrate on configurations specific to the driver.

Data Types

  • INT16
  • UINT16
  • INT32
  • UINT32
  • INT64
  • UINT64
  • FLOAT
  • DOUBLE
  • BIT
  • STRING

Address format

AREA ADDRESS[.BIT][.LEN[H][L]]

.BIT

Only available for non-bit type area, which means reading the specified binary bit of the specified address, the binary bit index interval is [0, 15].

.LEN[H][L]

When the data type is string type, .LEN indicates the length of the string; you can optionally fill in H and L to indicate two-byte orders, and the default is the byte order of H.

PLC Area

AreaDATA TYPEATTRIBUTEREMARK
Xuint16, uint32, uint64, bitread/writeExternal input
Yuint16, uint32, uint64, bitread/writeExternal output
Ruint16, uint32, uint64, bitread/writeInternal relay
Tuint16, uint32, uint64, bitread/writeTimer
Cuint16, uint32, uint64, bitread/writeCounter
Luint16, uint32, uint64, bitread/writeLink relay
DTallread/write (bit type read-only)Data register DT
LDallread/write (bit type read-only)Link data register LD
FLallread/write (bit type read-only)File register FL
S----Timer/counter set value area SV
K----Timer/counter elapsed value area EV
IXallread/write (bit type read-only)Index register IX
IYallread/write (bit type read-only)Index register IY
IDallread/write (bit type read-only)Index register ID

Example Addresses

AddressData typeDescription
X0bitX Area, Address 0
X1bitX Area, Address 1
Y0bitY Area, Address 0
Y1bitY Area, Address 1
DT100int16D Area, Address 100
DT1000uint16D Area, Address 1000
DT200uint32D Area, Address 200
DT10floatD Area, Address 10
DT20doubleD Area, Address 20
DT20.0bitD Area, Address 20, 0 bit
DT20.2bitD Area, Address 20, 2 bit
DT1002.16LstringD Area, Address 1002, String length 16, Byte order L
DT1003.16stringD Area, Address 1003, String length 16, Byte order H

Use Case

You can use Neuron Panasonic Mewtocol plugin to connect FP-XH C30T, for details, see Connect to FP-XH C30T.

Data Monitoring

After completing the point configuration, you can click Monitoring -> Data Monitoring to view device information and control devices. For details, refer to Data Monitoring.