Connect to Southbound Devices

This chapter will introduce how to use Neuron to support the transformation of various industrial protocols, enabling data collection from different types of southbound devices. This section will use PeakHMI Slave Simulators to simulate Modbus TCP devices, demonstrating the complete process of adding and configuring southbound devices.

Modbus TCP is a version of the Modbus protocol based on Ethernet, which uses TCP/IP for communication.

Add a Southbound Device

Create a southbound device node to connect to a real device or simulator.

In Configuration -> South Devices, click Add Device to add a device node. Or you can choose to configure the plugin through a template. This demonstration will use the plugin method as an example.

  • Name: Fill in the name of the device, such as modbus-tcp-1;
  • Plugin: Select the plugin of modbus-tcp from the drop-down box.

After clicking Create, you will be directed to the Device Configuration page, where we will configure the parameters needed for Neuron to establish a connection with the device. You can also click on the Device Configuration icon on the southbound device card to start the configuration.

Device Configuration

This page includes the parameters required for Neuron to establish a connection with the device.

TIP

To ensure communication between Neuron and southbound devices, please make sure the IP and Port are correctly set and the firewall is turned off.

Click the Application Configuration button on the device card to configure. For configuration items of the Modbus TCP driver, see Southbound Drivers - Modbus TCP.

After clicking Submit, the configuration of the southbound device is completed, and the application card automatically enters the Running state.

After the southbound device is successfully created, a newly created card will appear in the southbound management interface, as shown in the following figure.

south-devices

Device Cards

On the South Devices page, you can choose to display southbound applications in a list or card view. Here uses the device card as an example to explain the various options.

  • Name: The unique name provided by the user for the device.

  • Application Configuration: Click this button to enter the configuration interface for setting the parameters required for Neuron to connect to southbound devices.

  • Edit: Starting from version 2.5.0, Neuron supports updating node names. To change the name of the target node, click the Edit icon, and in the pop-up dialog box, modify the node name.

  • Data Statistics: Statistics for the node.

  • DEBUG Log: Print the DEBUG level log for the current node. After ten minutes, Neuron will revert to printing the default level of logs.

  • Delete: Remove this node from the device list.

  • Status: Displays the current status of the device node. Currently, the node has five working statuses.

    • Initialize: After adding a device for the first time, it will enter the initialization state.
    • Configure: Enter the device configuration and enter the configuration state.
    • Ready: After successful configuration, enter the ready state.
    • Running: The application is in running status.
    • Stop: The application is stopped.
  • Connection Status: Displays the connection status of the device. After adding the group and tag, Neuron will connect to the device to collect data, and the connection status will show Connected.

  • Plugin: Displays the name of the plugin module used by the device.

Configure Data Groups and Tags

In Neuron, a "tag" represents a specific data point within a device, enabling data extraction or injection. "Group" is a collection of user-interest tags that facilitate data exchange between nodes. After adding the south devices, you can start to add tags and groups to start the data acquisition.

TIP

Neuron supports the batch configuration of groups and data tag points through Excel files. For details, see Batch Group/Tag Configuration.

Create a Group

Create a group of tags, which collect and report the data of the same group at the same frequency

Click the new device node to enter the group list management interface, and click Create to create the group.

  • Name: Fill in the name of the Group, such as group-1.
  • Interval: Set the frequency of collection and reporting of this group of tags, in milliseconds, 100 means that the whole group of points is collected every 100 ms and the value of the whole group of points is reported once.

TIP

An interval is a duration of time utilized for data collection from equipment and subsequent reporting to MQTT. The minimum setting available is 100ms. However, when there is a large volume of data being collected, the data monitoring interface may report an error indicating an invalid point value. In such cases, it would be appropriate to increase the interval value.

Add Tags to the Group

Add the device tags to be collected, including tag address, tag attribute, tag type, etc.

Click the Tag List icon in the group to enter the tag list management interface.

Select the Create icon to enter the tag page.

tags-add

  • Name: This is a unique identifier that you provide for the tag, such as tag1.
  • Attribute: Dropdown to select the tag attribute, for example, read, write, subscribe, supporting the configuration of multiple tag types.
    • Read: Used to read data
    • Write: Used to write data
    • Subscribe: Only sends messages when data changes. For example, the default data is 0, when the data changes to 2, a message will be sent
  • Type: The type of data stored at this tag. This could be integer, float, string, or boolean. Choose the type according to your device data.
  • Address: Fill in the tag address, for example, 1!40001. 1 represents the tag site number set in the Modbus simulator, and 40001 represents the tag register address. For detailed instructions on how to use the driver address, please refer to South Device - Modbus TCP.
  • Decimal: not filled in by default; when the tag attribute includes read, you can set the Decimal. In this case, device value * decimal = display value.
  • Bias: not filled in by default; when the tag attribute is read, it supports setting Bias. At this time, device value + Bias = display value.
  • Precision: Configure the precision when the point type is float or double. The precision range is 0 to 17.
  • Description: not filled in by default.

TIP

Once the tag is created and the equipment card is operational, the connection status should display as Connected. If the status remains as Disconnected, please execute the following commands in the terminal of the Neuron runtime environment. This will help verify if the Neuron runtime environment can access the appropriate IP address and port.

bash
telnet <Running IP on PC side of Modbus simulator> 502

Data Monitoring

After completing the point configuration, you can click Monitoring -> Data Monitoring to view device information and control devices. For details, refer to Data Monitoring.

Operation and Maintenance

Data Statistics

In the device card or device column, you can click on the data statistics chart to view the application running status, and the state of received and sent data.

south-statistics

Key field descriptions are as follows:

ParameterDescription
last_rtt_msThe time interval of sending and receiving an instruction, in milliseconds
send_bytesThe total number of bytes of sent instructions
recv_bytesThe total number of bytes of received instructions
tag_reads_totalThe total number of instructions for reading points, including failed reads
tag_read_errors_totalThe total number of instructions for failed reads
group_tags_totalThe total number of points in the group
group_last_send_msgsThe number of messages sent by calling a group timer once
group_last_timer_msThe time to call a group timer once, in milliseconds
link_stateNode connection status
DISCONNECTED = 0
CONNECTED = 1
running_stateNode state
INIT = 1
READY = 2
RUNNING = 3
STOPPED = 4

Troubleshooting

If there are any issues with device operation, you can click on the DEBUG log chart. The system will automatically print DEBUG level logs for that node and switch back to the system default log level after ten minutes. Later, you can click on System Information -> Logs at the top of the page to view logs and perform troubleshooting. For a detailed interpretation of system logs, see Managing Logs.