Modbus RTU FAQ
Unable to Read Tag Value, Error Code 3002
- Enable DEBUG logging, check the log, inspect the data flow, and verify if the device has responded with data. If there is a response, check if the data is correct (serial devices may produce exceptions when multiple upstream masters collect data).
- Check if the station number is correct.
- Verify if the address is correct (Modbus address for Neuron starts from 1).
- Some devices may not support reading a single point at a time, so all points need to be configured (Neuron automatically optimizes batch reading).
- Serial wiring issues.
- Incorrect serial port configuration.
- The device supports Modbus TCP protocol instead of Modbus RTU. Try using the Modbus TCP plugin.
Tag Value Invalid, Error Code 3008
- The device is offline, and data cannot be updated.
- The device does not respond with data within a certain period.
- The device supports Modbus TCP protocol instead of Modbus RTU. Try using the Modbus TCP plugin.
Tag Value Read does not Match Expectations
- Incorrect data type.
- Incorrect byte order.
- Presence of multiple upstream masters collecting data results in data corruption.
- The DTU has enabled registration or heartbeat packets, causing Neuron to consider data flow data as incorrect.
- The device actively uploads data, but the standard Modbus only supports requesting and then responding with corresponding data.
- The device supports Modbus TCP protocol instead of Modbus RTU. Try using the Modbus TCP plugin.